Developers Diversified of Tenn. v. Tokio Marine & Fire Ins. Co. ( 2018 )


Menu:
  •                           NOT RECOMMENDED FOR PUBLICATION
    File Name: 18a0044n.06
    No. 16-6615
    FILED
    Jan 23, 2018
    DEBORAH S. HUNT, Clerk
    UNITED STATES COURT OF APPEALS
    FOR THE SIXTH CIRCUIT
    DEVELOPERS DIVERSIFIED OF TENNESSEE,                         )
    INC., n/k/a DDR CORP.,                                       )
    )
    Plaintiff/Counter-Defendant/Appellee,                )
    ON APPEAL FROM THE
    )
    UNITED STATES DISTRICT
    v.                                                           )
    COURT FOR THE MIDDLE
    )
    DISTRICT OF TENNESSEE
    TOKIO MARINE & FIRE INSURANCE CO.,                           )
    )
    Defendant/Counter-Plaintiff/Appellant.               )
    BEFORE: MOORE, WHITE, and DONALD, Circuit Judges.
    HELENE N. WHITE, Circuit Judge. Defendant/Counter-Plaintiff/Appellant Tokio
    Marine & Fire Insurance Co. (Tokio) appeals the district court’s judgment in favor of
    Plaintiff/Counter-Defendant/Appellee Developers Diversified of Tennessee, Inc. (“DD”)1 in this
    declaratory-judgment action to determine DD’s liability as landlord for property damage
    resulting from a partial roof collapse over retail space leased by Tokio’s insured, Sports
    Authority, Inc. (“SA”). We AFFIRM.
    1
    When this action was commenced, Appellee was known as “Developers Diversified of Tennessee, Inc.”
    At some point, it changed its name to “DDR Corp.”
    No. 16-6615, Developers Diversified of Tenn., Inc. v. Tokio Marine & Fire Ins. Co.
    I. BACKGROUND
    A. Facts
    We summarized the underlying facts in our prior opinion.
    [SA] entered into a lease agreement [(“the Lease”)] in January 1998 with Hendon
    Investments (Hendon) to lease retail space in a Brentwood, Tennessee, yet-to-be-
    built shopping center. Hendon assigned the [L]ease to Service Hendon Cool
    Springs Associates (Service Hendon). Service Hendon retained an architectural
    firm, Pieper, O’Brien, Herr Architects, Ltd. (Pieper), to design the shopping
    center, including [SA’s] space. The Lease provided that [SA’s] building would be
    designed and constructed in general accordance with prototypical drawings and
    specifications submitted by [SA]. Pieper submitted drawings and specifications,
    which [SA] approved. Sub-contractor Holland Roofing installed the roof.
    Construction of the shopping center was completed, and [SA] occupied the leased
    premises in September 1998. Plaintiff DD entered into a purchase and sale
    agreement in July 1998 to acquire the shopping center from Service Hendon,
    although the transaction did not close until after construction was completed in
    April 2000. Pursuant to the agreement, Service Hendon assigned and DD
    assumed [SA’s] [L]ease. The “Assignment and Assumption of Leases” between
    DD and Service Hendon provided that DD “assumes and agrees to perform all of
    the terms, covenants, obligations and conditions of the Lease . . . in respect of the
    period from and after the date of this Assignment.”
    After acquiring the shopping center in April 2000, DD, through a property
    management company, retained Foresight Consulting, Inc., and CHM Roof
    Consultants to inspect the roof. Neither reported any problem or defect to DD.
    Following a severe rain storm in May 2003, part of the roof over [SA’s] store
    collapsed and merchandise was damaged.
    Developers Diversified of Tennessee, Inc. v. Tokio Marine & Fire Ins. Co., 415 F. App’x 653,
    655 (6th Cir. 2011) (record citations omitted). Tokio, as SA’s insurer, covered the loss of
    merchandise, and as SA’s subrogee, asserted a right to reimbursement from DD. DD then
    brought the instant declaratory-judgment action to determine its obligations to Tokio. DD
    argued that SA had not provided it with notice that the roof was in need of repair, and, therefore,
    DD was not in default of the Lease’s covenant to repair.          Tokio “counterclaimed for its
    -2-
    No. 16-6615, Developers Diversified of Tenn., Inc. v. Tokio Marine & Fire Ins. Co.
    subrogated damages, alleging that [DD] breached the Lease by failing to correct defects in the
    [r]oof’s drainage system and . . . by failing [to] maintain the [r]oof (generally and in a [c]ode-
    complaint state), which allowed rainwater to pond on the [r]oof[,]” causing the collapse.
    (Appellant’s Br. at 2.)
    B. The Lease
    The key provisions of the Lease provide:
    6. DRAWINGS AND SPECIFICATIONS
    A. Generally. Tenant’s Building and the Site Improvements shall be constructed
    by Landlord . . . in accordance with the Approved Drawings and Specifications[.]
    ***
    F. Construction of the Building and Site Improvements/Incorporation of Materials
    and Components from Tenant’s Prototypical Store Drawings and Specifications.
    Tenant’s Prototypical Store Drawings and Specifications, the Approved Drawings
    and Specifications and the Approved Site Improvement Drawings and
    Specifications shall constitute a part of this Lease; provided however that
    Landlord shall construct Tenant’s Building in accordance with the Approved
    Drawings and Specifications (or any revisions thereto approved pursuant to the
    provisions of Article 6.D hereof) and shall construct the Site Improvements in
    accordance with the Approved Site Improvement Drawings and Specifications
    (or any revisions approved pursuant to the provisions of Article 6.E hereof.)
    Notwithstanding the approval by Tenant of the Approved Drawings and
    Specifications or the Approved Site Improvement Drawings and Specifications,
    Landlord shall incorporate all of the materials and components specified in
    Tenant’s Prototypical Store Drawings and Specifications into the Approved
    Drawings and Specifications and the Approved Site Improvement Drawings and
    Specifications and to the extent such materials and components are not
    incorporated or replaced by a substitute written approval by Tenant in its sole and
    absolute discretion, Tenant shall receive a credit to be applied toward Tenant
    Requested Change Orders and if no such Tenant Requested Change Orders are
    received or if Tenant’s credits are not offset by Tenant Requested Change Orders,
    then Landlord shall pay Tenant an amount equal to the credit within sixty
    (60) days of the Date of Occupancy[.]
    ***
    -3-
    No. 16-6615, Developers Diversified of Tenn., Inc. v. Tokio Marine & Fire Ins. Co.
    8. GUARANTEE OF MATERIALS. Landlord shall unconditionally guarantee all
    work performed by or for Landlord in the construction of Tenant’s Building and
    the Site Improvements against defective workmanship and materials for the
    period of one (1) year from the commencement of the Lease Term. On the Date
    of Occupancy, Landlord shall assign to Tenant any and all guarantees of
    workmanship and materials which it is required to receive (by Tenant’s
    Prototypical Store Drawings and Specifications, the Approved Drawings and
    Specifications and the Approved Site Improvement Drawings and Specifications)
    relating to items Tenant is required to repair and maintain, provided, however that
    notwithstanding such assignment, landlord shall use its commercially reasonable,
    diligent and good faith efforts to enforce such one (1) year guaranty and any other
    unexpired non-assignable warranties and guarantees relating to such items at
    Tenant’s request and on Tenant’s behalf. Landlord’s assignment to Tenant of any
    and all guarantees of workmanship and materials for items Tenant is required to
    repair and maintain pursuant to the terms of this Lease shall not relieve Landlord
    of any obligations relating thereto which are Landlord’s obligation pursuant to the
    provisions hereof. Within thirty (30) days of the Date of Occupancy, Landlord
    shall provide Tennant with close out books assigning the warranties and
    guaranties required herein to Tenant.
    ***
    12. LANDLORD’S REPRESENTATIONS, WARRANTIES AND COVENANTS
    A. Representations, Warranties and Covenants.        Landlord hereby represents,
    warrants and covenants as follows:
    ***
    (ii) Prior to and as a condition of the Date of Delivery of Possession, Landlord
    shall have substantially completed and prior to and as a condition to the Date of
    Occupancy Landlord shall have completed Tenant’s Building in accordance with
    the Approved Drawings and Specifications (and any modifications thereto
    requested and approved by Tenant in accordance with Article 6.D. hereof) and
    shall have delivered to Tenant a final Certificate of Occupancy for Tenant’s
    Building and the Site Improvements [.]
    ***
    14. REPAIRS AND MAINTENANCE
    A. Tenant’s Building. Tenant shall make and pay for all maintenance,
    replacement and repair necessary to keep Tenant’s Building in a good state of
    repair and in tenantable condition except for the items set forth in Article 17
    hereof (which are designated as Landlord’s responsibility) and the following
    maintenance, replacement or repair which shall remain the Landlord’s sole
    -4-
    No. 16-6615, Developers Diversified of Tenn., Inc. v. Tokio Marine & Fire Ins. Co.
    responsibility unless Tenant, its employees, contractors, agents or invitees, caused
    the need for such repair, in which event Tenant shall pay only its contributing
    factor if Landlord gives notice to Tenant of Landlord’s reasonable allocation of
    the costs between Tenant and other parties to be named by Landlord in said
    notice, and Tenant reasonably agrees to such allocation. Said notice shall also
    include the percentage allocation to each such contributing party for each item of
    repair. In the event of a dispute between Landlord and Tenant with respect to said
    allocation, Landlord shall be entitled to pursue such remedies as are available
    under this Lease or at law.
    (i) all maintenance, replacement and repair to the roof, slab . . . ,
    outer walls, interior walls (to the extent of structural maintenance,
    replacement and repair) and structural portions of the Building . . .
    which shall be necessary to maintain the Building in a safe, dry
    and tenantable condition and in good order and repair . . . ;
    ***
    (iv) all maintenance, replacement and repair due to the acts,
    omissions, neglect or negligence of Landlord, or any other owner,
    occupant or tenant in the Shopping Center and each of their
    employees, agents, or contractors;
    ***
    (vi) all maintenance, replacement and repair to the gutters and
    downspouts of the Building necessary to keep the same in good
    order and repair;
    ***
    (vii) the costs of correcting defects in or inadequacies of the initial
    design or construction of Tenant’s Building, the Site
    Improvements or the Common Areas or repair and replacement of
    any of the original materials or equipment in Tenant’s Building,
    the Site Improvements or the Common Areas required as a result
    of such defects or inadequacies;
    ***
    [¶5] Landlord shall use reasonable and good faith efforts to stage, sequence, and
    perform any repair, maintenance or replacements to the Building to minimize the
    disruption of and interference with Tenant’s business and operations and upon
    commencement of such repair, maintenance or replacement shall be continuously
    prosecuted and all repairs, maintenance and replacements to the Building
    performed by or on behalf of the Landlord shall be performed in a good,
    -5-
    No. 16-6615, Developers Diversified of Tenn., Inc. v. Tokio Marine & Fire Ins. Co.
    workmanlike and lien free manner and in compliance with all applicable legal and
    governmental and quasi-governmental requirements . . . .
    ***
    17. GOVERNMENTAL REGULATIONS. Tenant shall observe and comply with
    all requirements, rules, orders and regulations of the federal, state and municipal
    governments or other duly constituted public authority affecting Tenant’s
    Building, including the making of structural and non-structural alterations, insofar
    as they are due to Tenant’s specific occupancy and not retail occupancy in
    general; provided, however, in the event such rules, orders and regulations shall
    . . . (b) require structural or non-structural changes which are not due to the
    specific use of the premises by Tenant and are due to the general retail nature of
    the use, then and in . . . such event[ ], the same shall be complied with by
    Landlord at its sole cost and expense. Tenant shall have the right, however, to
    contest, without cost to Landlord, the validity or application of any such rule,
    order or regulation required to be complied with by Tenant in accordance with the
    foregoing . . . .
    (Appellant’s App’x Vol. II, at 281- 316.)
    C. The Roof and Construction Defects
    SA’s roof’s framework
    consisted of trusses . . . designed to span a distance between load points (e.g.
    columns). The trusses that spanned from the front west wall (“Wall D1”) to rear
    east walls (“Wall D5” and “Wall D6”) were denominated “joists,” and the trusses
    that spanned from the north side wall (“Wall DA”) and south side wall (“DF
    Wall”) were denominated “joist girders.”
    (Appellant’s Br. at 25.) Joist girders supported joists, which supported the roof, and “where the
    joist girders met the [masonry] walls, they were embedded in [them].” (R. 407, PID 8003.) The
    exterior walls extended up above the roof plane, forming a “parapet” which enclosed the roof.
    (Appellant’s Br. at 27.) Because the roof was flat, the architect sloped the roof as it progressed
    from the front to the rear of the building, “[t]o drain the rainwater that would otherwise be
    trapped by th[e] [parapet] walls.” (Id.)
    -6-
    No. 16-6615, Developers Diversified of Tenn., Inc. v. Tokio Marine & Fire Ins. Co.
    The [r]oof was additionally and more drastically sloped along its sides (Walls DA
    and DF) – a slope that tapered center as the roof progressed from front to rear.
    The combined effect of these slopes directed all rainwater to a collection basin at
    the center rear of the [b]uilding where five crickets (submembrane projections
    designed to divert water) were supposed to direct rainwater to and through five
    unobstructed 6" x 18" scuppers (masonry-block sized outlets [for draining water]
    installed through the parapet walls and level with the roof surface), and off the
    [r]oof.
    (Id. at 27-28 (record citations omitted).)
    Tokio maintains that the roof failed because it did not accord with the original design in
    the following ways: (1) the number and the location of the scuppers were inverted: two were
    installed on Wall D6 when three were called for by the building’s design, and three were
    installed on Wall D5 when two were called for by the design; (2) although the design called for
    the Wall D6 scuppers to be only six inches lower than those on Wall D5, the constructed slope
    made the differential ten inches; (3) the crickets called for by the design were not constructed;
    (4) concrete blocks were installed in the throat of the Wall D6 scuppers, restricting the flow of
    water off the roof; and (5) four-inch tall ballast-retaining bars were installed in front of the
    scuppers, blocking them. According to Tokio, construction of the building’s walls also did not
    accord with the design because “the masonry column built into the [b]uilding’s rear wall [(‘The
    D6/DC Masonry Column’)], which supported the joist girder that collapsed, should have been
    topped with a reinforced concrete cap but was, instead, topped with a masonry cap.”2
    (Appellant’s Br. at 10, 34.)
    2
    Tokio also maintains that a “bond beam,” designed to support the joists near the rear walls of the building,
    was not installed. However, Tokio concedes that the missing bond beam played no role in the collapse.
    -7-
    No. 16-6615, Developers Diversified of Tenn., Inc. v. Tokio Marine & Fire Ins. Co.
    D. Procedural History
    The district court granted summary judgment to DD, and Tokio appealed. In Developers
    Diversified of Tennessee, Inc. v. Tokio Marine & Fire Ins. Co., 415 F. App’x 653 (6th Cir. 2011),
    we affirmed the district court’s order granting DD summary judgment on Tokio’s claim that DD
    is liable for the failure to construct the building in accordance with the Lease,3 and reversed and
    remanded for the district court to address the remaining issues, whether DD: 1) failed to maintain
    and repair the roof, as required by Lease ¶14(A)(i); 2) failed to remediate construction defects as
    required by Lease ¶14(A)(vii); 3) failed to ensure that all maintenance was performed in a good,
    workmanlike manner, as mandated by Lease ¶14(A)¶5; and 4) failed to assume responsibility for
    its roof inspectors’ alleged negligence, as required by Lease ¶14(A)(iv). We also remanded for
    the district court to decide in the first instance whether DD failed to comply with any applicable
    government regulations by allegedly maintaining the building in a code-violative state, in
    contravention of Lease ¶¶17 and 14(A)¶5. 
    Id. at 669.
    On remand, following a bench trial, the district court declared that DD had no duty to pay
    Tokio for any subrogated damages and dismissed Tokio’s counterclaims. This appeal followed.
    3
    We precluded liability for default under Lease ¶¶6(F) and 12(A)(ii) for failing to construct the building in
    accordance with the original design because DD “as a successor to Service Hendon’s interest in the leasehold,
    cannot be held liable for Service Hendon’s pre-assignment breach that was incapable of continuous or independent
    repetition subsequent to [DD’s] assumption of the Lease.” Developers Diversified, 415 F. App’x at 673.
    -8-
    No. 16-6615, Developers Diversified of Tenn., Inc. v. Tokio Marine & Fire Ins. Co.
    II. STANDARD OF REVIEW
    Where, as here, the district court has conducted a bench trial, we review the district
    court’s findings of fact for clear error and its conclusions of law de novo. Kalamazoo River
    Study Grp. v. Menasha Corp., 
    228 F.3d 648
    , 652 (6th Cir. 2000) (citing Schroyer v. Frankel,
    
    197 F.3d 1170
    , 1173 (6th Cir. 1999)). “Clear error occurs only when [the court is] left with the
    definite and firm conviction that a mistake has been committed. If there are two permissible
    views of the evidence, the factfinder’s choice between them cannot be clearly erroneous.” Caver
    v. Straub, 
    349 F.3d 340
    , 351 (6th Cir. 2003) (internal quotation marks and citation omitted).
    Even greater deference is required when the findings of fact rest upon credibility determinations.
    Anderson v. City of Bessemer City, N.C., 
    470 U.S. 564
    , 575 (1985).
    III. ANALYSIS
    Tokio argues on appeal that (1) the district court erred in finding that Tokio failed to
    prove by a preponderance of the evidence that any alleged breach of the Lease was the direct and
    proximate cause of the roof collapse; (2) the district court erred in concluding that constructive
    notice of the construction defects that allegedly caused the collapse was a precondition to finding
    that DD breached the obligations established by Lease ¶¶14 and 17, and, even if constructive
    notice was a necessary precondition, the district court erred in concluding that DD did not have
    such notice; (3) the district court erred in concluding that Lease ¶8’s one-year workmanship-and-
    materials guarantee precluded finding that DD breached Lease ¶¶14 and 17; (4) the district court
    -9-
    No. 16-6615, Developers Diversified of Tenn., Inc. v. Tokio Marine & Fire Ins. Co.
    erred by concluding that SA’s Tenant Estoppel Certificate waived all claims for breaches of the
    Lease arising from patent construction defects; and (5) the district court erred in concluding that
    SA’s failure to complain about the alleged construction defects after occupying the building
    waived all claims for breaches of Lease ¶¶14 and 17.4
    Because the district court did not clearly err in finding that Tokio failed to prove
    causation and notice, we affirm.5
    A. Applicable Law
    All agree that Tennessee law applies. First Am. Nat’l Bank v. Fidelity & Deposit Co. of
    Md., 
    5 F.3d 982
    , 984 (6th Cir. 1993). Under Tennessee law, “[t]he legal effect of the terms of a
    lease are governed by the general rules of contract construction.” Planters Gin Co. v. Fed.
    Compress & Warehouse Co., 
    78 S.W.3d 885
    , 889 (Tenn. 2002). Our initial task in construing a
    lease “is to ascertain and give effect to the intent of the parties.”                     Allmand v. Pavletic,
    
    292 S.W.3d 618
    , 630 (Tenn. 2009) (citation omitted). Courts determine the parties’ intent by
    examining the plain and ordinary meaning of the written words that are “contained within the
    four corners of the contract.” 84 Lumber Co. v. Smith, 
    356 S.W.3d 380
    , 383 (Tenn. 2011)
    4
    Tokio also argues that the district court’s opinion should be read with a “jaundiced eye” because the
    district court copied verbatim from DD’s proposed factual findings and conclusions of law. (Appellant’s Br. at 6-7.)
    Thus, according to Tokio, entire sections of the district court’s decision reflect DD’s lawyers “zeal and advocacy”
    rather than “the product of a disinterested mind.” (Id.) However, this does not change our standard of review. See
    
    Anderson, 470 U.S. at 572
    (“[W]hen the trial judge adopts proposed findings verbatim, the findings are those of the
    court and may be reversed only if clearly erroneous.”) (citations omitted).
    5
    The district court found in DD’s favor on several alternative bases. However, because causation and
    notice are independently sufficient to affirm the district court’s judgment, we need not address the remaining,
    alternative bases for the district court’s judgment or discuss the court’s ruling regarding the Tenant Estoppel
    Certificate, one-year workmanship-and-materials guarantee, and waiver.
    -10-
    No. 16-6615, Developers Diversified of Tenn., Inc. v. Tokio Marine & Fire Ins. Co.
    (citation omitted); see also Warren v. Metro. Gov’t of Nashville & Davidson Cty., Tenn.,
    
    955 S.W.2d 618
    , 623 (Tenn. Ct. App. 1997) (“We are precluded from making new contracts for
    the parties by adding or deleting provisions.”) (citation omitted). The literal meaning of the
    contract language controls if the language is clear and unambiguous. 
    Allmand, 292 S.W.3d at 630
    . However, if the terms are ambiguous in that they are “susceptible to more than one
    reasonable interpretation,” courts must apply other established rules of construction to aid in
    determining the contracting parties’ intent.      Planters Gin 
    Co., 78 S.W.3d at 890
    (citation
    omitted).
    In Tennessee, “[i]n actions of contract, generally speaking, the damages are limited to the
    natural and proximate consequences of the breach complained of, and damages remotely or
    consequentially resulting therefrom, or merely speculative damages, cannot be claimed.” Walker
    v. Ellis, 
    33 Tenn. 515
    , 523 (1853); see also Missouri Portland Cement Co. v. J. A. Jones Const.
    Co., 
    323 F. Supp. 242
    , 246 (M.D. Tenn. 1970), aff’d sub nom. J. A. Jones Const. Co. v. Englert
    Eng’g Co., 
    438 F.2d 3
    (6th Cir. 1971) (“[A] plaintiff is entitled to recover damages for breach of
    contract if the . . . defendant’s breach of contract was the direct and proximate cause of the
    damages which plaintiff has allegedly sustained, without concurring or contributing fault on the
    part of the plaintiff.”) (internal quotation marks and citation omitted).
    -11-
    No. 16-6615, Developers Diversified of Tenn., Inc. v. Tokio Marine & Fire Ins. Co.
    B. Causation
    In its “Answer and Third Amended Counter-Claim” (Answer), Tokio alleged that
    the combination of the aggressive slope, absent crickets, collector boxes without
    overflow protection, and retainer bars (the “Roof Defects”), each compromised
    the roof’s drainage system, impeded the roof’s ability to shed water, and allowed
    water to pond on the lowest portion of the roof where the collapse eventually
    occurred.
    (R. 271, PID 3364, ¶33.)       Tokio also alleged that the Roof Defects “violated applicable
    governmental regulations, including the Brentwood Municipal Building Code (‘Code’).” (Id.
    ¶34.) Further, according to Tokio’s Answer, the roof’s drainage system was compromised by
    “[t]he existence of debris on the roof, including timber, concrete blockings, sheet metal and any
    other debris[.]” (Id. at 3365, ¶43.) However, notwithstanding Tokio’s initial allegations of
    several different Roof Defects, Tokio’s pre-trial theory focused on the “retainer bars blocking
    scupper openings, debris on the roof, and violation of Code Ordinances . . . .” (R. 366, PID
    6321.)
    All agree that it was Tokio’s burden to prove that any of the alleged defects and Code
    violations caused the roof to collapse.
    1.
    Tokio’s theory at trial, as stated by Tokio’s main expert, David Wright, was that the
    accumulation of eighteen inches of rainwater on the roof caused it to collapse. Both parties’
    hydrology experts agreed that in order for eighteen inches of rainwater to pool on SA’s roof,
    -12-
    No. 16-6615, Developers Diversified of Tenn., Inc. v. Tokio Marine & Fire Ins. Co.
    three and a half to four of the five scuppers would have to have been completely blocked or
    clogged when it began to rain.
    The district court did not credit Wright’s opinion that the accumulation of eighteen inches
    of rainwater caused the collapse.      The district court observed that “Wright, on numerous
    occasions, testified contrary to previous deposition testimony. He also attempted to evade
    questions asked of him by [DD]’s counsel. He often spoke in highly technical terms, without
    explaining his testimony in a logical, coherent, and understandable manner.” (R. 407 PID 8051.)
    “Wright changed his theory several times during the course of this case.” (Id.) Indeed, Wright
    admitted at trial that his initial report, which he later withdrew, contained erroneous conclusions.
    He explained that, at the time he prepared the report, he did not have certain “critical
    information” and documents from Vulcraft, the manufacturer of the joists and joists girders.
    Wright did not, however, mention in his report that he needed those documents. Wright’s second
    report also contained errors, which he admitted at trial. He again explained that, at the time he
    completed his second report, he had not yet received the Vulcraft documentation.              Again,
    however, he failed to mention that in his report. Wright revised his analysis two more times after
    that.   The district court was entitled to take the shifting positions into consideration in
    determining what weight to give to Wright’s opinions.
    The district court credited instead the testimony of DD’s expert, William Dickey, who
    testified that “[f]or the joist girder that collapsed to have failed solely as a result of the weight
    -13-
    No. 16-6615, Developers Diversified of Tenn., Inc. v. Tokio Marine & Fire Ins. Co.
    load of an excessive water accumulation on the roof, the depth of ponding on the roof would
    have had to be over 22 inches at the rear (D6) wall.” (R. 407 PID 8015 (citing Dickey Trial
    Test., R. 381, PID 7491-93).) According to both parties’ hydrology experts, to achieve a
    theoretical water accumulation of over twenty-two inches, every one of the five scuppers would
    have to be completely blocked or clogged. But the district court observed that “[n]o evidence
    was introduced that any, let alone 4 to 5, of the 5 roof scuppers were completely blocked or
    clogged with debris at the time of the partial collapse.” (R. 407, PID 8014.) The district court
    credited Dickey’s testimony that it was “not conceivable” that the scuppers were “one hundred
    percent blocked.” (R. 407, PID 8039 (quoting Dickey Trial Test. R. 380, PID 7403).) Dickey
    testified, in part:
    I have no data at all that would give me any indication that two or three or four
    scuppers would become a hundred percent blocked and put a huge amount of
    water on this roof and cause the joist girder to collapse under an extreme overload
    situation, was not something I was going on.
    (R. 380, PID 7411.) Tokio’s expert, Thomas Allen, also testified that he had no information or
    evidence that any of the five scuppers was completely blocked. Even Tokio’s main expert,
    Wright, testified that he was not aware of any evidence to support the conclusion that any of the
    five scuppers was blocked, and that “it’s impossible for [him] to predict exactly what the depth
    of the water was at the time of the collapse.” (R. 378, PID 6982.)
    -14-
    No. 16-6615, Developers Diversified of Tenn., Inc. v. Tokio Marine & Fire Ins. Co.
    As to any debris clogging the scuppers, the district court again credited Dickey’s
    testimony:
    I could not conceive of the scuppers being 100 percent blocked before the
    rainstorm started, which is the basis of the hydraulics analyses that have been
    done. The water estimates from those analyses are all upper-bounds. They all
    overestimate the water. And unless somebody went out there with pieces of
    plywood and nailed them over the scuppers, there is no way I can concede [sic] of
    them being a hundred percent blocked.
    (R. 380, PID 7401.) Moreover, a roof inspection performed just one week before the collapse
    revealed only a few concrete blocks on the roof, which, as DD’s expert testified, “wouldn’t
    float.” (Douglass Dep., Appellee’s App’x, Vol. XIV, at 2687.) Although the report notes that
    there was “debris scattered throughout the roof area[,]” it contains only one photograph of the
    debris, depicting the concrete blocks. (Appellee’s App’x, Vol. IX, at 1627.) The inspector,
    Elliott Buss, testified that had there been any other debris, he would have taken a picture of it and
    included it in his report. He also testified that he did not see anything blocking the scupper
    openings. Finally, Tokio admitted that “[n]o complete blocking or complete clogging of any
    scupper on the subject roof was ever observed or reported either before or after the collapse by
    anyone during any pre-collapse roof inspections, including the roof inspection performed just
    one week before the partial roof collapse.” (R. 308, PID 4255-56.) Thus, the district court did
    not clearly err when it found that “[n]o evidence was introduced that any, let alone 4 to 5, of the
    5 roof scuppers were completely blocked or clogged with debris at the time of the partial
    collapse.” (R. 407, PID 8014.)
    -15-
    No. 16-6615, Developers Diversified of Tenn., Inc. v. Tokio Marine & Fire Ins. Co.
    2.
    Tokio also argued at trial that the retainer bars contributed to the blocking of the
    scuppers; the district court, however, disagreed and found that the retainer bars were
    “appropriate” and “necessary.”             The district court credited the deposition testimony of the
    representatives of Holland Roofing of Nashville, Inc. (Holland), the company that installed SA’s
    single-ply, ballasted roof and that “had worked on ‘hundreds’ of roofs[.]” (R. 407, PID, 8005
    (citing Stark (Former president of Holland) Dep., Appellee’s App’x, Vol. XVIII, at 3472).)
    Holland’s representatives testified that the retainer bars installed on SA’s roof were standard bars
    manufactured by the roof manufacturer, Carlisle, and were what Holland typically installed on
    scuppers.6
    The representatives of the companies involved in the inspections of SA’s roof, Foresight
    Consulting, Inc. (Foresight) and CHM Roof Consultants, Inc. (CHM), also agreed that some
    form of scupper guard is needed for a ballasted roof. And, before the collapse, neither company
    had recommended the removal of the installed scupper guards. The district court also noted the
    deposition testimony of Scott Christenson, CHM’s inspector who had nearly thirty-five years of
    experience as a roofer, roof inspector, and roof consultant, regarding his inspection of SA’s roof
    in August 2001:
    6
    Jim Stark, Holland’s former president, who worked in the roofing industry for approximately twenty
    years, also testified that “he expects to see a gravel stop or a gravel-retaining bar in front of scupper[s] on a ballasted
    roofing system.” (R. 308, PID 4267.) Grant Stout of Pieper, O’Brien, Herr, one of the original architects of the
    building, agreed that with a single-ply, ballasted roof, it is necessary to have some protection in front of scuppers to
    prevent rock, ballast, and other materials from blocking the down-spouts.
    -16-
    No. 16-6615, Developers Diversified of Tenn., Inc. v. Tokio Marine & Fire Ins. Co.
    A strong thunderstorm rolled in during his inspection of the SA roof, causing a
    heavy downpour for several minutes. When Mr. Christenson resumed his
    inspection several minutes following the conclusion of the thunderstorm, he found
    that the rain water had drained from the roof and that there was no standing water
    or ponding on that roof. As a result of his observation of the roof completely
    draining following a heavy thunderstorm, Mr. Christenson determined that the SA
    roof drained adequately.
    (R. 407, PID 8007-08 (record citations omitted).)
    The district court additionally credited the deposition testimony of Elliot Buss, a
    Foresight inspector who inspected the roof on April 29, 2003, six days before the collapse.
    During the inspection, Buss saw no evidence of ponding on the roof or that the roof was not
    draining properly, and did not see anything requiring a consultation with or referral to an
    engineer or an architect; he also had no concerns about the retaining bars.
    Finally, according to Tokio’s expert, the installed retainer bars had a “very minimal” and
    “minuscule” effect on the amount of water accumulation; the data shows a difference of only
    .10 foot in predicted water ponding between the hydrological models with and without the
    retainer bars. (R. 378, PID 7023-26, Appellee’s App’x, Vol. XI, at 2041-42.) Thus, the district
    court did not clearly err when it found that Tokio failed to prove that the bars had any
    meaningful impact on the alleged accumulation of water on the roof.
    3.
    Tokio next argues that because Dickey, DD’s expert whom the district court found
    credible, testified that a wall defect likely caused the collapse, the district court should have
    concluded that Tokio established causation. Dickey indeed testified that the failure to install a
    -17-
    No. 16-6615, Developers Diversified of Tenn., Inc. v. Tokio Marine & Fire Ins. Co.
    concrete wall cap, as the original construction design mandated, and the installation instead of a
    weaker, grout-reinforced masonry cap, “most likely” allowed the “DC” joist girder to “f[a]ll out
    of the [D6] wall.” (R. 360, PID 7336.) Nevertheless, Tokio’s argument fails.
    First, viewed in context, Dickey’s testimony about the missing concrete cap appears to be
    merely a hypothesis. Dickey also testified:
    It’s important to understand, nobody knows the cause. Nobody knows a whole lot
    of things about this. As you know, the materials that collapsed, we were calling
    that the debris, was removed. We did not have an opportunity to review it or look
    at it. We have all agreed it would be of tremendous help in a forensic analysis to
    be able to view those parts. We did not see those. So we’re trying to do a
    forensic analysis here by photograph and by speculation. And that’s -- a bit hard
    . . . . [A]s I said, the cause is unknown[.]
    (R. 380, PID 7323, 7335.) Dickey’s uncertainty about the cause of the collapse is clear from the
    record. In one portion of his testimony, he pointed to “numerous construction errors associated
    with how the joists and the joist girders were fastened to the masonry wall.” (R. 380, PID 7324
    (emphasis added).) He opined that it was possible that “the bearing plate was too small,”
    (R. 381, PID 7480), or “the material [was not] the right grade[,]” or a joist girder “g[o]t bent or
    kinked during the process of erecting [the wall][,]” or a joist girder was “burned slightly or
    completely removed in order to fit in some mechanical equipment[.]” (R. 380, PID 7336.) He
    testified, “[t]here’s a whole lot of things that could have happened. And if we had examined the
    debris that was on the ground, we would know the answer to all of these possibilities.” (Id.)
    Second, Tokio argued at trial that “the DC Joist Girder could not have ‘fallen out’ of the
    D6 Wall as Dickey claimed.” (Appellant’s Br. at 45.) According to Tokio, Dickey’s theory is
    -18-
    No. 16-6615, Developers Diversified of Tenn., Inc. v. Tokio Marine & Fire Ins. Co.
    “implausible” and contradicted by documents and objective evidence.            (Id. at 51 (citation
    omitted).) Moreover, Tokio’s expert opined that the alleged wall defect, “the missing Concrete
    Cap[,] played no causative role in the collapse.” (Id. at 44.) Thus, at trial, Tokio argued against
    the very theory it now claims satisfied its burden of proof.
    Third, Dickey’s hypothesis about the cause of the collapse was undermined by his
    concessions that it was not based on any calculations.
    4.
    Finally, as to any alleged building Code violations, the district court found none. (R. 407,
    PID 8014 (“There was no code violation, defect, or dangerous condition associated with the roof
    drainage system.”).)    Tokio, however, argues that the district court erred by relying on a
    temporary Certificate of Occupancy (“COO”), issued by a city official, which stated that the
    building met the Code. Moreover, according to Tokio, the district court erred when it relied on
    lay testimony of a city official that the building was Code-complaint.
    It is true that “[the] interpretation of city and state building codes is a matter of law for
    resolution by the court and not a proper subject for testimony from at least that of a non-lawyer.”
    Smith v. Wal-Mart Stores, Inc., 
    167 F.3d 286
    , 295 (6th Cir. 1999). However, even if the district
    court erred by crediting the opinion of a city official, Tokio failed to introduce any evidence that
    -19-
    No. 16-6615, Developers Diversified of Tenn., Inc. v. Tokio Marine & Fire Ins. Co.
    any Code violations7 directly and proximately caused the collapse. For instance, Tokio argues
    that “the testimony of [DD’s] Code expert, William Pistrui, proves that the Building was not
    Code-complaint” because the roof did not have “a 4" deep, 8' wide band of ballast” along its
    walls.8 (Appellant’s Br. at 67.) However, Tokio presented no evidence that the absence of a 4"
    deep, 8' wide band of ballast played a role in the collapse of the roof.
    5.
    In sum, the district court found that “[e]ven assuming for purposes of argument that [DD]
    did commit a material breach or default under the Lease, Tokio failed to show by a
    preponderance of the evidence that any such breach or default was the direct and proximate
    cause of the roof collapse or any damages suffered by Tokio.” (R. 407, PID 8052.) We are not
    “left with the definite and firm conviction,” 
    Caver, 349 F.3d at 351
    , that the district court clearly
    erred when it found that Tokio did not prove causation.
    7
    And even Tokio’s experts testified that the retainer bars did not violate any Code provisions. (See also
    R. 407, PID 8052 (“Tokio did not show by a preponderance of the evidence that there was any “code violation” in
    connection with the SA building, or that any such default directly and proximately caused the partial roof
    collapse.”).).
    8
    Pistrui in fact stated in his investigative report that “there [was] no Code violation, no defect, and no
    dangerous condition associated with the roof drainage system[,] including the scupper bar. Indeed, the roof drainage
    system exceed[ed] Code requirements.” (Appellant’s App’x, Vol. IV, at 713.)
    -20-
    No. 16-6615, Developers Diversified of Tenn., Inc. v. Tokio Marine & Fire Ins. Co.
    C. Constructive Notice
    1.
    Tokio next argues that the district court erred in concluding that constructive notice of the
    construction defects that allegedly caused the collapse was a prerequisite to liability under Lease
    ¶¶14 and 17.
    Relying on Marshalls of Nashville, Tenn., Inc. v. Harding Mall Assocs., Ltd., 
    799 S.W.2d 239
    , 244-45 (Tenn. Ct. App. 1990), we previously held that constructive notice is a prerequisite
    for recovering damages under Lease ¶14(A)(i). Developers Diversified, 415 F. App’x at 663.
    We did not, however, reach the question whether constructive notice is a prerequisite to liability
    for breach of the obligations established by any other provision of the Lease. We held only that
    “to the extent that Marshalls bears on the resolution of these independent breaches, the district
    court should read Marshalls as imposing only a constructive notice requirement.” 
    Id. at 664.
    Although the district court did not consider whether Marshalls had any bearing on the
    remaining obligations under the Lease, it nevertheless correctly concluded, albeit without
    analysis, that constructive notice applied.
    As we previously recognized, “some notice requirement is widely recognized and
    applied, including in modern-day cases.” Developers Diversified, 415 F. App’x at 661 (citing
    Cause of Action Against Lessor for Failure to Repair or Maintain Leased Commercial Premises,
    4 Causes of Action 2d 785 (2008); 49 Am.Jur.2d, Landlord and Tenant § 463; C.J.S. Landlord
    -21-
    No. 16-6615, Developers Diversified of Tenn., Inc. v. Tokio Marine & Fire Ins. Co.
    & Tenant § 838.)9 We also observed that the “common-law notice requirement does not apply
    where it conflicts with the express terms of the parties’ contract.” 
    Id. at 663.
    Here, the Lease is
    silent regarding any notice requirement in relation to ¶¶14 and 17; thus, the Lease does not
    conflict with the common-law rule requiring some notice. As we previously stated, “‘[w]here a
    landlord is obligated to make repairs during the term, actual or constructive notice of the need for
    repair is necessary to put the landlord in default on such obligation, unless he or she agreed to
    repair without notice[.]’” 
    Id. at 662
    (emphasis added) (quoting C.J.S. Landlord & Tenant
    § 836). See also Hines v. Wilcox, 
    96 Tenn. 328
    , 
    34 S.W. 420
    , 421 (1896) (stating that although
    the common-law rule “does not place upon the landlord the obligation of an insurer or warrantor
    by contract,” “[t]he tenant may have more extensive rights if she expressly contracts” for them)
    (emphasis added). Nothing in the instant Lease suggests that Service Hendon and SA intended
    to abrogate the common-law notice rule or that Service Hendon “agreed to repair without
    notice.”10
    Moreover, other sections of the Lease contain provisions specifically dispensing with any
    notice requirement. See, e.g., Lease ¶12(B) (“Notwithstanding the foregoing, Landlord’s failure
    to satisfy the requirements of Article 12.A. (vi) hereof, shall not be subject to any notice and
    9
    See also Delatte v. S. Mark Realty Partners, Ltd., No. 01A01-9504-CV-00141, 
    1996 WL 17148
    , at *3
    (Tenn. Ct. App. Jan. 19, 1996) (holding that, in the context of a negligence claim pursued by a tenant against his
    landlord, “[l]iability does not ensue until the landlord has notice, actual or constructive, and a reasonable opportunity
    to repair the defect”).
    10
    Cf. Gordon v. Williams, 
    986 S.W.2d 470
    , 473 (Mo. Ct. App. 1998) (finding that the parties waived a
    common-law notice requirement because the commercial lease expressly provided that tenants waive any notice
    requirements before landlords could bring action to repossess leasehold)
    -22-
    No. 16-6615, Developers Diversified of Tenn., Inc. v. Tokio Marine & Fire Ins. Co.
    cure period as provided in Article 12.B. (ii)[.]”) (emphasis added); Lease ¶12(C) (“In the event
    the Date of Occupancy occurs and Landlord shall violate any of the representations, warranties
    or covenants contained in this Lease, including Article 12 hereof, or fail to fulfill any of the
    covenants contained in this Lease during the Lease Term, Tenant shall immediately (and without
    any additional notice or cure period) pay Substitute Rent, in arrears by the fifth of each month
    for the Gross Sales of the prior month and in addition (without any notice or cure period) have
    the option of . . . .”) (emphases added); Lease ¶16 (“If the utility service is interrupted due to the
    default or negligence of Landlord, its agents or employees, there shall be a prorated abatement of
    Annual Minimum Rental and all other charges payable by Tenant pursuant to this Lease based
    on the amount of time and area deemed nonfunctional by Tenant (such abatement to occur
    without any notice and cure period).”) (emphasis added). These provisions indicate that, under
    some circumstances, the original contracting parties intended to deviate from the rule requiring a
    “notice and cure period.” Neither Lease ¶14 nor ¶17 contains similar language modifying the
    otherwise applicable common-law rule.
    Thus, we conclude that the original parties to the Lease did not intend to modify the
    common-law rule requiring at least constructive notice as a prerequisite to liability for breach of
    duties under the Lease. As such, the district court did not err as a matter of law when it applied
    constructive notice to the Lease provisions at issue.
    -23-
    No. 16-6615, Developers Diversified of Tenn., Inc. v. Tokio Marine & Fire Ins. Co.
    2.
    Tokio next argues that even if constructive notice11 was a necessary precondition, the
    district court clearly erred in concluding that DD did not have such notice. We disagree.
    Tokio’s expert, Fitts, admitted that a visual inspection of the roof and drainage system
    would not have alerted anyone to a Code violation or a roof defect. Bruce Reed, another Tokio
    expert, was unable to point to any specific defect or Code violation that “the world’s best [pre-
    assumption-of-lease] inspection” would have uncovered. (R. 378, PID 7131-38.) The district
    court also accurately observed that “[n]othing in the roof inspection reports . . . , including for an
    inspection performed just one week before the May 5, 2003 collapse, mentioned or alerted [DD]
    to any significant problem with either the roof or its drainage system, let alone any possible
    danger of an imminent partial roof collapse.” (R. 407, PID 8014.) Further, citing DD’s expert’s
    deposition, the district court noted that “[a]bsent destructive testing, [DD] did everything it
    reasonably could to inspect and maintain the roof drainage system.” (R. 407, PID 8050 (citing
    Pistrui Dep., Appellee’s App’x, Vol. XVII, at 3219-20).) Dickey also opined that the purported
    weak connection of the joist girder to the wall was a latent construction error that could only be
    ascertained by destructive testing and not by ordinary inspection.
    11
    In Tennessee, constructive notice is “information or knowledge of a fact imputed by law to a person
    (although he may not actually have it), because he could have discovered the fact by proper diligence, and his
    situation was such as to cast upon him the duty of inquiring into it.” Kirby v. Macon County, 
    892 S.W.2d 403
    , 409
    (Tenn. 1994) (quoting BLACK’S LAW DICTIONARY 1062 (6th Ed. 1990)). “[C]onstructive notice can be established
    by proving that the dangerous condition existed for a sufficient length of time that the premises owner, by exercising
    due care, should have discovered the dangerous condition.” Williams v. Linkscorp Tenn. Six, LLC, 
    212 S.W.3d 293
    ,
    296 (Tenn. Ct. App. 2006) (citing Simmons v. Sears, Roebuck & Co., 
    713 S.W.2d 640
    , 641-42 (Tenn. 1986)).
    -24-
    No. 16-6615, Developers Diversified of Tenn., Inc. v. Tokio Marine & Fire Ins. Co.
    Tokio argues, however, that the facts compel a conclusion that DD had constructive
    notice of the missing concrete cap.      Tokio maintains that had the building been properly
    constructed with a concrete rather than a masonry cap,
    the concrete cap would have extended from the rear wall’s interior face to its
    exterior face; would have been made of concrete, which is smooth and thus
    distinguishable from the surrounding masonry blocks; would have been 10" x 10",
    rather than 8" x 16", the standard size of a masonry block; would have been
    visible from ground level; and – having not been installed – would have put [DD]
    on inquiry notice to determine whether any other potential problems may have
    existed where the relevant joist girder connected to the relevant masonry column.
    (Appellant’s Br. at 11-12 (citing Dickey’s trial testimony).)
    Tokio’s argument fails. To be sure, Dickey admitted that a concrete cap does not “have
    the same face as a masonry block,” (R. 381, PID 7470), and drew a rectangle on a photograph
    exhibit to indicate where the concrete cap would have been. However, neither Dickey nor any of
    Tokio’s experts opined whether the difference between a 10" x 10" cap and an 8" x 16" cap atop
    the masonry columns on the underside of the roof would have been noticeable upon reasonable
    inspection from any vantage point. The answer is not apparent from the photographic exhibit on
    which Dickey drew, and Dickey opined that reviewing the original design and any “post-
    construction as-built work . . . done in the building” would not have revealed any construction
    errors. (R. 380, PID 7339.) Further, Tokio offered no evidence to support its theory that DD had
    constructive notice of the missing cap. This is not surprising given that Tokio maintained at trial
    that “the missing Concrete Cap played no causative role in the collapse.” (Appellant’s Br. at 44.)
    -25-
    No. 16-6615, Developers Diversified of Tenn., Inc. v. Tokio Marine & Fire Ins. Co.
    In sum, we cannot conclude that the district court clearly erred when it held that “Tokio
    has not shown by a preponderance of the evidence that DD ha[d] constructive notice of any
    defective condition,” (R. 407 PID 8052), because the district court’s finding is “plausible in light
    of the record viewed in its entirety.” 
    Anderson, 470 U.S. at 573-74
    .
    IV. CONCLUSION
    Accordingly, we AFFIRM the judgment of the district court.
    -26-