Mt. Morris Mutual Insurance Company v. EA Restoration, LLC ( 2020 )


Menu:
  •        COURT OF APPEALS
    DECISION                                    NOTICE
    DATED AND FILED                This opinion is subject to further editing. If
    published, the official version will appear in
    the bound volume of the Official Reports.
    October 21, 2020
    A party may file with the Supreme Court a
    Sheila T. Reiff        petition to review an adverse decision by the
    Clerk of Court of Appeals   Court of Appeals. See WIS. STAT. § 808.10
    and RULE 809.62.
    Appeal No.        2019AP2136                                        Cir. Ct. No. 2016CV310
    STATE OF WISCONSIN                                 IN COURT OF APPEALS
    DISTRICT II
    MT. MORRIS MUTUAL INSURANCE COMPANY,
    PLAINTIFF,
    DARREL J. MAYES,
    INVOLUNTARY-PLAINTIFF,
    V.
    EA RESTORATION, LLC AND WEST BEND MUTUAL INSURANCE COMPANY,
    DEFENDANTS-THIRD-PARTY
    PLAINTIFFS-APPELLANTS,
    SANDOVAL CONTRACTING & REMODELING, LLC AND ROCKFORD MUTUAL
    INSURANCE COMPANY,
    DEFENDANTS,
    V.
    THE CHIMNEY GUY, LLC,
    THIRD-PARTY DEFENDANT-RESPONDENT.
    No. 2019AP2136
    APPEAL from an order of the circuit court for Fond du Lac County:
    RICHARD J. NUSS, Judge. Affirmed.
    Before Neubauer, C.J., Reilly, P.J., and Davis, J.
    Per curiam opinions may not be cited in any court of this state as precedent
    or authority, except for the limited purposes specified in WIS. STAT. RULE 809.23(3).
    ¶1       PER CURIAM. EA Restoration, LLC, (EA) seeks contribution
    and/or indemnification from The Chimney Guy, LLC, for fire damage following a
    home restoration. The circuit court granted summary judgment to The Chimney
    Guy, and EA now appeals. We affirm as no reasonable jury could find negligence
    on behalf of The Chimney Guy, and even if some negligence is assumed, we
    conclude that public policy considerations preclude The Chimney Guy’s liability
    in this case.
    Background
    ¶2       On January 6, 2015, a fire occurred at Darrel J. Mayes’ home. To
    repair his home, Mayes hired EA, who subcontracted with The Chimney Guy and
    Sandoval Contracting & Remodeling, LLC (Sandoval).
    ¶3       In April 2015, The Chimney Guy installed a chimney system in
    Mayes’ home. The chimney system started on the first floor, ran through the
    second floor, and ended above the roof. This chimney system consisted of a stove,
    chimney pipe, ceiling support package, universal adaptor, flashing storm collar,
    rain cap, and roof support brace kit. The Chimney Guy installed the ceiling
    support package between the first-story ceiling and the second-story floor. A
    ceiling support package functions to maintain a two-inch clearance between the
    chimney pipe and combustibles. The Chimney Guy also installed a chase to
    2
    No. 2019AP2136
    enclose the chimney pipe running through the second story. The Chimney Guy
    did not install an attic insulation shield, as the chase enclosure served the same
    purpose—to prevent debris from entering the ceiling support box.
    ¶4       After The Chimney Guy completed the chimney system installation,
    Sandoval removed the existing roof and installed a new metal roof on Mayes’
    home. During this process, Sandoval had to remove two metal braces and flashing
    that supported the chimney pipe. Additionally, Sandoval may have had to remove
    the top two sections of the chimney pipe, the chimney cap, the storm collar, and
    other components. Neither EA nor Sandoval advised The Chimney Guy of this
    additional work above the chimney’s ceiling support package or asked The
    Chimney Guy to inspect the chimney system to ensure proper clearances.
    ¶5       A second fire occurred at Mayes’ home on January 7, 2016. Mayes’
    insurer, Mt. Morris Mutual Insurance Company, paid for the damage from this
    second fire and filed a subrogation claim against EA, Sandoval, and their
    respective insurers, alleging breach of contract and negligence. EA filed a third-
    party complaint seeking indemnification and/or contribution from The Chimney
    Guy.
    ¶6       EA’s expert, Donald VanOss, a certified fire and explosion
    investigator, testified that the likely cause of the second fire was debris in the
    ceiling support package, although he could not rule out the roof line as the point of
    origin. VanOss could not determine how and exactly when the debris entered the
    support box, but he found no evidence to suggest the debris was present in the
    ceiling support package when The Chimney Guy completed the chimney
    installation.   Neither VanOss nor any other parties’ experts opined that The
    Chimney Guy deposited debris into the ceiling support box.
    3
    No. 2019AP2136
    ¶7        VanOss also opined that EA or Sandoval should have contacted a
    certified chimney inspector or installer after Sandoval completed its roof work, as
    an inspector or installer could have verified that Sandoval properly reconnected
    the chimney pipe and maintained the two-inch clearances from combustibles.
    VanOss also opined that a chase enclosure serves as an appropriate substitution for
    an insulation shield.
    ¶8        The circuit court granted The Chimney Guy’s motion for summary
    judgment, concluding that EA’s claims against The Chimney Guy were
    speculative (“a bunch of but-ifs”). EA appeals.
    Standard of Review
    ¶9        We review a grant or denial of summary judgment de novo. Bain v.
    Tielens Constr., Inc., 
    2006 WI App 127
    , ¶5, 
    294 Wis. 2d 318
    , 
    718 N.W.2d 240
    .
    Summary judgment is appropriate when there is no genuine issue as to any
    material fact and the moving party is entitled to judgment as a matter of law. WIS.
    STAT. § 802.08(2) (2017-18).1
    Discussion
    ¶10       EA first contends that there is a genuine issue of material fact as to
    whether The Chimney Guy’s work led to combustibles entering the ceiling support
    package. We disagree. EA offers no evidence other than speculation that The
    Chimney Guy deposited the debris into the ceiling support package. EA also
    argues that there is a genuine issue of material fact as to whether The Chimney
    1
    All references to the Wisconsin Statutes are to the 2017-18 version.
    4
    No. 2019AP2136
    Guy breached its duty of care when it failed to install an attic installation shield.
    This argument is dispelled by EA’s own expert, VanOss, who testified that the
    chase was an appropriate alternative to the insulation shield. The installation
    manual for the chimney system installed by The Chimney Guy also provided that
    an enclosure is an alternative to the shield. No reasonable jury could find The
    Chimney Guy was negligent when it chose to install a chase in place of an attic
    installation shield or that in doing so, it caused or allowed combustibles to remain
    in the system.2
    ¶11     Denying recovery due to the speculative nature of any basis on
    which a jury could find causation finds further legal support from public policy
    considerations Wisconsin has long adhered to in limiting tort recovery. Meaning
    that, even if we were to assume negligence based on EA’s speculations arising
    from the use of the chase enclosure, public policy considerations would preclude
    The Chimney Guy’s liability in this case.
    ¶12     We may deny liability in cases of proven or assumed negligence
    upon any of the following six public policy grounds: “(1) ‘the injury is too remote
    from the negligence’; (2) the recovery is ‘wholly out of proportion to the
    culpability of the negligent tort-feasor’; (3) the harm caused is highly
    extraordinary given the negligent act; (4) recovery ‘would place too unreasonable
    a burden’ on the negligent tort-feasor; (5) recovery would be ‘too likely to open
    2
    Another expert, Christopher Andritsch, said the installation shield was required by the
    manual, and it would have prevented the second fire by preventing the combustible materials
    from entering the ceiling support box. Our review of the manual does not support the contention
    that an installation shield was required. Moreover, no expert opined that The Chimney Guy’s
    installation of a chase enclosure around the chimney pipe from the chimney support box to the
    roof was improper or negligent.
    5
    No. 2019AP2136
    the way to fraudulent claims’; and (6) recovery would enter into ‘a field that has
    no sensible or just stopping point.’” Hornback v. Archdiocese of Milwaukee,
    
    2008 WI 98
    , ¶49, 
    313 Wis. 2d 294
    , 
    752 N.W.2d 862
     (citation omitted). We may
    refuse to impose liability upon public policy grounds without full resolution of a
    cause of action by trial. 
    Id.
    ¶13    The first factor—whether the plaintiff’s injury is too remote from the
    defendant’s negligence—restates “the old chain of causation test.”        Cefalu v.
    Continental W. Ins. Co., 
    2005 WI App 187
    , ¶20, 
    285 Wis. 2d 766
    , 
    703 N.W.2d 743
    . A finding of remoteness essentially is “a determination that a superseding
    cause should relieve the defendant of liability.” Id., ¶21. To assess remoteness,
    we consider “the time, place or sequence of events” and “whether ‘the chain of
    causation was direct and unbroken.’” Kidd v. Allaway, 
    2011 WI App 161
    , ¶14,
    
    338 Wis. 2d 129
    , 
    807 N.W.2d 700
     (citation omitted); see also Beacon Bowl, Inc.
    v. Wisconsin Elec. Power Co., 
    176 Wis. 2d 740
    , 762, 
    501 N.W.2d 788
     (1993).
    ¶14    Here, the fire damage was too remote from any alleged negligence
    of The Chimney Guy. Specifically, the sequence of events and the broken chain
    of causation points to remoteness. After The Chimney Guy installed the chimney
    system, Sandoval altered The Chimney Guy’s work. Neither EA nor Sandoval
    advised The Chimney Guy of the alteration to its work. Neither EA nor Sandoval
    asked The Chimney Guy or any other certified chimney inspector or installer to
    verify proper clearances were maintained after they had altered The Chimney
    Guy’s work. Sandoval’s alterations broke any chain of causation between The
    Chimney Guy’s work and the fire damage. Thus, the damage from the second fire
    was too separate and removed from any alleged negligence of The Chimney Guy.
    6
    No. 2019AP2136
    ¶15     As no genuine issues of material fact exist as to The Chimney Guy’s
    negligence, we affirm the circuit court’s grant of summary judgment to The
    Chimney Guy.3
    By the Court.—Order affirmed.
    This     opinion     will    not       be   published.       See    WIS. STAT.
    RULE 809.23(1)(b)5.
    3
    Given our decision, we need not address The Chimney Guy’s procedural and
    evidentiary objections, which were not raised before the circuit court, including its contention that
    late filings precluded consideration and that certain expert testimony was inadmissible.
    7
    

Document Info

Docket Number: 2019AP002136

Filed Date: 10/21/2020

Precedential Status: Non-Precedential

Modified Date: 9/9/2024